FR-Lead Free PVC Insulated Single Core Fixed Wire
- Home
- Building Cables
- FR-Lead Free PVC Insulated Single Core Fixed Wire
OUR PRODUCTS
Building Cable
Flexible Cable
Submersible Cable
Communication Cable
Data & Communication Cable
Solar Cable
Automotive Cable
Harmonished (HAR) Cable
Braided Cable
Fire Survival Cable
FR-Lead Free PVC Insulated Single Core Fixed Wire (IS 694)
Lead Free PVC Insulated Single Core Unsheathed Flexible CABLES Volatge grade Up to 1100 VOLTS IS 694:2010
Application
Suitable for wiring commercial and domestic buildings. They are also used for industrial
applications.
Technical Data
- Approvals: IS 694 marked, FIA/TAC
- Voltage Grade: Up to and Including 1100V
- Conductor: Bright annealed bare electrolytic grade Copper conductor as per IS 8130:2013
- Insulation:Q-FLX Brand provides flat cables with both Type A FR-LF PVC compound for general purpose or Type C (HR -FR LF) in case of HR PVC compound as per IS 5831 applied around each conductor.
Insulation Conformity: IS 5831, Type A/Type C - FR LF
- Colours Marking Packing: Red, Yellow, Blue, Black, Green
- Marking: The cables are printed with marking of “Q-FLX CABLES 1100V SQMM IS 694 ISI CM/L 1115123
- Packing: The cables are packed as 90m coil from 1 sq.mm up to 70 sq.mm. Longer length available on request.
Product Features
101 % Copper Conductivity, (IACS) | Extra Annealing |
Longer Flexible Life | 100% Lead Free |
Technical Specification of Single Core , PVC Insulated Unsheathed Solid Stranded Copper Cable 1100V.
Nominal Area of Conductor | Number and Nominal Diameter of Wire | Nominal Thickness of insulation | Maximum Overall Diameter | Current Carrying Capacity | Conductor Resistance at 20°C (Maximum) |
mm2 | mm | mm | mm | (Amps) | Ohm/km |
1 | 1 /1.13* | 0.7 | 2.7 | 12 | 18.1 |
1.5 | 3 /0.80** | 0.7 | 33 | 16 | 12.1 |
2.5 | 3 /1.04** | 0.8 | 4.0 | 22 | 7.41 |
4 | 7 / 0.85** | 0.8 | 4.6 | 29 | 4.61 |
6 | 7 / 1.04** | 0.8 | 5.2 | 37 | 3.08 |
10 | 7 / 1.35** | 1.0 | 6.7 | 51 | 1.83 |
16 | 7 / 1.70** | 1.0 | 7.8 | 68 | 1.15 |
25 | 19 / 1.30** | 1.2 | 9.7 | 86 | 0.727 |
35 | 19 / 1.53** | 1.2 | 10.9 | 110 | 0.524 |
50 | 19 / 1.78** | 1.4 | 12.8 | 145 | 0.387 |
70 | 37 / 1.55** | 1.4 | 14.6 | 200 | 0.268 |
*As per Class 1 Conductors of IS 8130:2013** As per Class 2 Conductors of IS 8130:2013 Conforms to IS 694: 2010.
Note: The number and Diameter of the conductor strands are for reference only. The size of the conductor is determined by its resistance. it may vary within the limits of related Classes and tables of IS 8130:2013.
The above data is approximate and subject to manufacturing tolerance