Heat Resistant PVC Insulated Single Core Flexible Cable

Lead Free PVC Insulated Single Core Unsheathed Flexible CABLES Volatge grade Up to 1100 VOLTS IS 694:2010
Application
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations.
Technical Data
  • Specification: BS 6231 Type CK
  • Temperature Range : -25°C to +90 °C (105°C for 15000 hours)
  • Conductor: Class 5 flexible plain copper conductor to BS EN 60228:2005 (previously BS6360).
  • Insulation: PVC (Polyvinyl Chloride)Type TI3 to BS EN 50363-3. HR PVC 105 C
  • Colour: Black, red, blue, yellow, green / yellow, grey, brown, orange, white, violet, green, pink
  • Marking: Q-FLX CU/PVC “SIZE” “VOLTAGE GRADE” “RATED TEMPERATURE” “YEAR” COUNTRY OF ORIGIN
  • Packing: Coil in 100 and 200 m in polythene wrapping. Longer length available on request.
  • Voltage rating:
    a) Nominal voltage : – 600/ 1000V
    a) Test voltage : – 4000 V
  • Minimum Bending Radius: < 8mm : 4 x cable diameter, > 8mm to 12mm : 5x Outer dimension, >12mm : 6 x outer dimension
Product Features
Special heat resistant insulationHigh current carrying capacity
Less heat energy radiationHigh flexibility
Excellent resistant to moisture, abrasion, grease, oil. Excellent mechanical & electrical properties
Insulation is highly thermal stable
TECHNICAL INFORMATION
BS 6231 CK (90°c)
Nominal cross sectional area of conductorNominal
insulation thickness
Mean overall diameterMax conductor resistance at 20°C
Lower LimitUpper Limit
sq.mmmmmmmmΩ /km
0.50.82.43.039.0
0.750.82.63.126.0
1.00.82.73.319.5
1.50.83.03.613.3
2.50.83.44.17.98
4.00.83.94.84.95
6.00.84.45.33.3
10.01.05.77.21.91
16.01.06.79.01.21
25.01.28.411.50.78
35.01.29.712.50.554
50.01.411.515.40.386
70.01.413.217.50.272
95.01.615.119.20.206
120.01.616.721.20.161
150.01.818.623.90.129
185.02.020.625.90.106
240.02.223.528.90.0801