Fire Survival Cables
Lead Free PVC Insulated Single Core Unsheathed Flexible CABLES Volatge grade Up to 1100 VOLTS IS 694:2010
Application
Fire Survival cables are used in sensitive environments to maintain circuit integrity during
and after any incidence of fire. They are designed to withstand high temperatures of a
defined period without any electrical breakdown.
Technical Data
- Approvals:
- Voltage Grade: 600/1000V
- Operature Temperature: – 40°C to + 90°C
- Heat Barrier: Glass Mica Tape Wrapped Over Conductor+
- Insulation: Crosslinked Polyethylene (XLPE) according to DS 7655-1.3
- Inner Covering Option: The laidup cores may be covered by an optional extrued inner covering separating tape.
- Inner Sheath: Extruded FRLS PVC
- Armour: Galvanised Steel Round Wire Armoured. (also available with Galvanised Steel Flat Strip Armour, dimensions and weights changes accordingly)
- Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1. Extruded FRLS PVC Outer Sheath, (other colour as per request).
- Colour: Black.
- Bending Radius: Min. 12 x Overall Diameter
- Test Voltage: 3500V AC at (20+5)°C
- Reference Standards: IEC 60331, IEC 60332, IEC 60754, BS 7846 ,BS 6387, EN 50290-2-27, EN 50288-7, BS7655, BS 7629-1, 1S7098,1S9968, IS 6380, IS 3675, IEC 60502.
- Marking: ELECTRIC CABLE 600/1000V BS 7846-F1 XYZ (NO. OF CORE x SQ.MM)
Note: The Marking of items shall be by embossing or indenting on the oversheath.
Conductor
- Annealed plain stranded copper conductor as per IEC 60228, Class-2.
- Mica Glass flame barrier tape.
- Inner Sheath.
Core Identification
- 2 core: brown, blue
- 3 core: brown, black, grey
- 4 core: blue, brown, black, grey
- 5 core: green-and-yellow, blue, brown, black, grey
- Above 5 core can be supplied with number printing
- (All cores: optional number printing)
Advantages
Longer service life | Efficient performance |
Able to withstand extreme temperature during fire | High level of mechanical protection and shielding |
High dielectric strengthFlame and UV resistant | Heat and moisture resistantChemical and radiation resistant(optional) |
TWO CORE 600/1000 V CABLE WITH STRANDARD COPPER CONDUCTOR
Nominal Cross-Sectional area of Conductor | Thickness of Insulation | Thickness of Extruded Bedding | Nominal Steel Normal Wire Diameter | Thickness of oversheath | Approx. Overall Diameter |
---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | mm |
1.5 | 0.6 | 0.8 | 0.9 | 13 | 13.1 |
25 | 0.7 | 0.8 | 0.9 | 1.4 | 14.2 |
THREE CORE 600/1000 V CABLE WITH STRANDARD COPPER CONDUCTOR
Nominal Cross-Sectional area of Conductor | Thickness of Insulation | Thickness of Extruded Bedding | Nominal Steel Normal Wire Diameter | Thickness of oversheath | Approx. Overall Diameter |
---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | mm |
1.5 | 0.6 | 0.8 | 0.9 | 13 | 13.7 |
25 | 0.7 | 0.8 | 0.9 | 1.4 | 15.2 |
Note: Conductor shall be a circular or compacted circular stranded conductor(Class 2)
TEST REQUIREMENTS FOR FLAME RETARDANT CABLES
TEST | FUNCTION | SPECIFICATION | VALUE |
---|---|---|---|
Critical Oxygen Index | To determine the percentage of oxygen required for combustion of insulating material at room temperature | ASTM-D:2863 IS 10810 (Part 58):1998 | Oxygen Index shall not be less than 29% |
Temperature Index | To determine at what temperature normal content of 21% in air will support combustion of insulating material | ASTM-D:2863 IS 10810 (Part 64): 2003 | Temperature Index should be minimum 250°C at 21% of Oxygen |
Smoke Density | To determine the (Light Transmission) Visibility during fire of insulating material | ASTM-D:2843 | Light Transmission >=60% of Avg |
Acid Gas Generation | To ascertain the HCL acid gas released by insulating material during fire. | IEC 60754-1 | <=20% of (by weight) |
Circuit Intergrity / Fire Survival TestI | To determine the ability of cable to maintain the circuit in flame at 750°C for at least 3 hours (950°C for 3 hours as per BS:6387) | IEC 60331-21 | Cable shall withstand 750°C flame temperature and maintains the circuit uninterruptedly.Also for 950°C as per CWZ can be offered |