    Fire Survival Cables

    Lead Free PVC Insulated Single Core Unsheathed Flexible CABLES Volatge grade Up to 1100 VOLTS IS 694:2010
    Application
    Fire Survival cables are used in sensitive environments to maintain circuit integrity during and after any incidence of fire. They are designed to withstand high temperatures of a defined period without any electrical breakdown.
    Technical Data
    • Approvals:
    • Voltage Grade: 600/1000V
    • Operature Temperature: – 40°C to + 90°C
    • Heat Barrier: Glass Mica Tape Wrapped Over Conductor+
    • Insulation: Crosslinked Polyethylene (XLPE) according to DS 7655-1.3
    • Inner Covering Option: The laidup cores may be covered by an optional extrued inner covering separating tape.
    • Inner Sheath: Extruded FRLS PVC
    • Armour: Galvanised Steel Round Wire Armoured. (also available with Galvanised Steel Flat Strip Armour, dimensions and weights changes accordingly)
    • Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1. Extruded FRLS PVC Outer Sheath, (other colour as per request).
    • Colour: Black.
    • Bending Radius: Min. 12 x Overall Diameter
    • Test Voltage: 3500V AC at (20+5)°C
    • Reference Standards: IEC 60331, IEC 60332, IEC 60754, BS 7846 ,BS 6387, EN 50290-2-27, EN 50288-7, BS7655, BS 7629-1, 1S7098,1S9968, IS 6380, IS 3675, IEC 60502.
    • Marking: ELECTRIC CABLE 600/1000V BS 7846-F1 XYZ (NO. OF CORE x SQ.MM)
      Note: The Marking of items shall be by embossing or indenting on the oversheath.
    Conductor
    • Annealed plain stranded copper conductor as per IEC 60228, Class-2.
    • Mica Glass flame barrier tape.
    • Inner Sheath.
    Core Identification
    • 2 core: brown, blue
    • 3 core: brown, black, grey
    • 4 core: blue, brown, black, grey
    • 5 core: green-and-yellow, blue, brown, black, grey
    • Above 5 core can be supplied with number printing
    • (All cores: optional number printing)
    Advantages
    Longer service lifeEfficient performance
    Able to withstand extreme temperature during fireHigh level of mechanical protection and shielding
    High dielectric strengthFlame and UV resistantHeat and moisture resistantChemical and radiation resistant(optional)
    TWO CORE 600/1000 V CABLE WITH STRANDARD COPPER CONDUCTOR
     
    Nominal Cross-Sectional area of ConductorThickness of InsulationThickness of Extruded BeddingNominal Steel Normal Wire DiameterThickness of oversheathApprox. Overall Diameter
    mm2mmmmmmmmmm
    1.50.60.8 0.9 1313.1
    250.7 0.80.91.414.2
    THREE CORE 600/1000 V CABLE WITH STRANDARD COPPER CONDUCTOR

     

    Nominal Cross-Sectional area of ConductorThickness of InsulationThickness of Extruded BeddingNominal Steel Normal Wire DiameterThickness of oversheathApprox. Overall Diameter
    mm2mmmmmmmmmm
    1.50.60.80.91313.7
    250.70.80.91.415.2
    Note: Conductor shall be a circular or compacted circular stranded conductor(Class 2)
    TEST REQUIREMENTS FOR FLAME RETARDANT CABLES
    TESTFUNCTIONSPECIFICATIONVALUE
    Critical Oxygen IndexTo determine the percentage of oxygen required for combustion of insulating material at room temperatureASTM-D:2863 IS 10810 (Part 58):1998Oxygen Index shall not be less than 29%
    Temperature IndexTo determine at what temperature normal content of 21% in air will support combustion of insulating materialASTM-D:2863 IS 10810 (Part 64): 2003Temperature Index should be minimum 250°C at 21% of Oxygen
    Smoke DensityTo determine the (Light Transmission) Visibility during fire of insulating materialASTM-D:2843Light Transmission
    >=60% of Avg
    Acid Gas GenerationTo ascertain the HCL acid gas released by insulating material during fire.IEC 60754-1<=20% of (by weight)
    Circuit Intergrity / Fire Survival TestITo determine the ability of cable to maintain the circuit in flame at 750°C for at least 3 hours (950°C for 3 hours as per BS:6387)IEC 60331-21Cable shall withstand 750°C flame temperature and maintains the circuit uninterruptedly.Also for 950°C as per CWZ can be offered