Download Brochure

    Thermoplastic Insulated Halogen Free Cables (LSZH) Low Smoke Zero halogen

    Lead Free PVC Insulated Single Core Unsheathed Flexible CABLES Volatge grade Up to 1100 VOLTS IS 694:2010
    Application
    Halogen-free single-core wires are used for installation in dry environments for wiring up lighting fixtures and units where valuable assets are to protected from further damage resulting from fire. These cables may be installed on, in and beneath plaster, as well as in closed installation ducts. For use in public places such as: hospitals, schools, museums, airports, bus terminals, shops in general, etc., as well as in computer rooms, offices, production plants, switchboard wiring, laboratories, etc.
    Technical Data
    • Specification: BS: EN -50525-3-3 1
    • Temperature Range : -30°C to +70°C
    • Conductor: Class 5 flexible plain / metal coated stranded according to EN 60228.
    • Insulation: Thermoplastic halogen-free compound type TI7 to EN 50363-7.
    • Colour: Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Green, Yellow or other colours
    • Marking: Q-FLX CU/PVC “SIZE” “VOLTAGE GRADE” “RATED TEMPERATURE” “YEAR” COUNTRY OF ORIGIN
    • Packing: Coil in 100 and 200 m in polythene wrapping. Longer length available on request.
    • Voltage rating:
      a) Nominal voltage : HO5Z1-K :300/500V, HO7Z1-K : 450/750 V
      a) Test voltage : HO5Z1—K : 2500 V, HO7Z1-K : 2500 V
    • Minimum Bending Radius: < 8mm : 4 x cable diameter, > 8mm to 12mm : 5x Outer dimension, >12mm : 6 x outer dimension
    Product Features
    Smoke density to acc. to EN 61034-2.Halogen free acc. to EN 50525-1, EN 60754-1.
    Corrosivity acc. to EN 60754-2.Ozone resistant according to EN 60811-2-1 or HD 505.2.1.
    Self-exfinguishing and flame retardant according to EN 60332-1-2.LSOH = Low Smoke Zero Halogen.
    TECHNICAL INFORMATION
    HO5Z1-K (300/500V)
    Nominal cross sectional area of conductorNominal
    insulation thickness
    Mean overall diameterMax conductor resistance at 20°C
      Lower LimitUpper Limit 
    sq.mmmmmmΩ /km
    0.50.62.12.539.0
    0.750.62.22.726.0
    1.00.62.42.819.5
     
    HO5Z-K (450/750 V)
    Nominal cross sectional area of conductorNominal
    insulation thickness
    Mean overall diameterMax conductor resistance at 20°C
    Lower LimitUpper Limit
    sq.mmmmmmmmΩ /km
    1.50.72.83.413.3
    2.50.83.44.17.98
    4.00.83.94.84.95
    6.00.84.45.33.3
    10.01.05.76.81.91
    16.01.06.78.11.21
    25.01.28.410.20.78
    35.01.29.711.70.554
    50.01.411.513.90.386
    70.01.413.2160.272
    95.01.615.118.20.206
    120.01.616.720.20.161
    150.01.818.622.50.129
    185.02.020.624.90.106
    240.02.223.528.40.0801