FR-LEAD FREE – FLAME RETARDANT (FR LF)
Lead Free PVC Insulated Single Core Unsheathed Flexible CABLES Voltage grade Up to 1100 VOLTS IS 694:2010
Application
Suitable for wiring in all types of residential and Commercial infrastructure, where fire and electrical safety is utmost important
Technical Data
- Approvals: IS 694 marked, FIA/TAC
- Voltage Grade: Up to and Including 1100V
- Conductor: Bright annealed bare electrolytic grade Copperconductor as per IS 8130:2013
- Insulation: Specially formulated Flame retardant LEAD-FREE. PVC Compound manufactured In-House by a team of technical experts conforming to IS 5831 which offers a High Oxygen Index and High-Temperature Index.
Insulation Conformity: IS 5831, Type A/Type D - FR-LF
- Colours Marking Packing: Red, Black, Green, Yellow, Blue or any other colour as per customer requirement.
- Marking: The cables are printed with the marking “Q-FLX CABLES 1100V SQMM FR- LF IS 694 ISI CM/L 1115123
- Packing: The cables are packed as 90m coil in protective cartons from 1 sq.mm to 6 sq.mm. Longer length available up on request.
Product Features
101 % Copper Conductivity, (IACS) | Extra Annealing |
100% Bunched Copper | 100% Lead Free |
Higher Oxygen Index | Higher Temperature Index |
Flame Retardant Properties (FR – LF)
TEST | FUNCTION | SPECIFICATION | VALUE |
Critical Oxygen Index | To determine the percentage of oxygen required for combustion of insulating material at room temperature | IS 10810 (Part 58): 1998 | Oxygen Index shall not be less than 29% |
Temperature Index | To determine at what temperature normal oxygen content of 21% in air will support combustion of insulating material | IS 10810 (Part 64): 2003 | Temperature Index should be minimum 250°C at 21% of Oxygen |
***Also meets the requirement of Flammability Test as per IS 694:2010
Technical Specification of Single Core, FR-LF PVC Insulated Unsheathed Cable 1100V
Nominal Area of Conductor | Number and Nominal Diameter of Wire | Nominal Thickness of insulation | Maximum Overall Diameter | Current Rating (Amps) | Maximum DC Conductor Resistance at 20°C | |
---|---|---|---|---|---|---|
mm2 | No./mm | mm | mm | Casing | Concealed | Ohm(fl)/km |
1 | 14 /03* | 0.7 | 3.2 | 14 | 13 | 18.1 |
1.5 | 22 /03* | 0.7 | 3.3 | 18 | 16 | 12.1 |
2.5 | 36 /03* | 0.8 | 4.0 | 24 | 20 | 7.41 |
4 | 56 /03 | 0.8 | 4.8 | 30 | 26 | 4.95 |
6 | 84 /03** | 0.8 | 5.3 | 38 | 33 | 3.30 |
***As per Class 2 Conductors of IS 8130:2013** Conforms to IS 694: 2010.
Note: The number and Diameter of the conductor strands are for reference only. The size of the conductor is determined by its resistance. it may vary within the limits of related Classes and tables of IS 8130:2013.
The values given above are subject to tolerances as per relevent standards.
Sample Card available on request 1.0 to 4.0 Sqmm