Multicore Round Cables

Lead Free PVC Insulated Single Core Unsheathed Flexible CABLES Volatge grade Up to 1100 VOLTS IS 694:2010
Application
Suitable for wiring in machines, control panels, Electric power supplies etc under typical electrical installations for wiring in various electrical installations in dry and damp interiors.
Technical Data
  • Approvals: IS 694 marked, FIA/TAC
  • Voltage Grade: Up to and Including 1100V
  • Conductor: Bright annealed bare electrolytic grade Copper conductor as per IS 8130:2013.
  • Insulation:The insulation is PVC compound Type D of general purpose as per IS 5831
Sheath: The sheath is of PVC compound Type ST3 in case of general purpose PVC.
  • Colour Code of Cores:
    • 2 core – Red and Black.
    • 3 core – Red, Black and Yellow-green/Red, yellow and blue.
    • 4 core – Red, yellow, blue and yellow-green/Red, Yellow, blue and black.
    • Note: Any other Colour up on specific request will be provided.
  • Sheath Colour: Black Any other colour as per customer requirement.
  • Packing: Standard Packing : Supplied in 100 Meter Coil Polythene Wrapping & Also available 300mtr, 500mtr & 1000mtr on non returnable Wooden Drum on request. Longer lengths available on request
  • Marking : The cables are printed with marking of “Q-FLX Cables (Size) Sq.mm x (Core) YY 1100V IS 694 ISLCM/L-1115123”
Product Features
101 % Copper Conductivity, (IACS)  Extra Annealing
100% Bunched Copper  Longer Service Life
Product Variants Availble
PRODUCT TYPESPECIFICATION
Normal PVC 70°CIS 694, IS 8130 :2013 Class 5 ,IS 5831 TYPE D Insulation & ST-3 Sheath
HR PVC 85°CIS 694, IS 8130 :2013 Class 5 ,IS 5831 TYPE C Insulation & ST-2 Sheath
FR PVC 70°CIS 694, IS 8130 :2013 Class 5 ,IS 5831 TYPE D Insulation + ST-3 (FR) Sheath
HR PVC 85°C + FRIS 694, IS 8130 :2013 Class 5 ,IS 5831 TYPE C Insulation + ST-2 (FR) Sheath
FR-LSHIS 694 IS 8130 :2013 Class 5 ,IS 5831 TYPE D Insulation + ST-3 (FR-LSH) Sheath
 
Technical Specification for PVC Insulated and PVC Sheathed Flexible Cables (Circular) with Copper conductor for working voltages up to and including 1100V
Nominal Area of
Conductor
Number and
Nominal Diameter
of Wire
Nominal Thickness
of insulation
Nominal Sheathing
Wall Thickness
Overall Dimension,
Maximum
Conductor
Resistance
at 20°C
(Maximum)
   Single CoreTwo CoreThree CoreFour CoreFive CoreSingle CoreTwo CoreThree CoreFour CoreFive Core 
mm2mmmmmmmmmmmmmmmmmmmmmmmmOhm/km
0.516 /0.200.60.90.90.90.90.94.36.97.38.08.739.00
0.7524 /0.200.60.90.90.90.90.94.57.37.78.49.226.00
132 /0.200.60.90.90.90.91.04.77.68.18.89.619.50
1.530 /0.250.60.90.90.91.01.05.48.99.410.411.413.30
2.550 /0.250.71.01.01.01.01.06.210.310.912.013.27.98
456 /0.300.81.01.01.01.01.16.811.612.413.615.34.95
684 /0.300.81.11.11.21.27.513.013.815.473.30
1080 /0.401.01.31.31.41.49.416.517.6919.51.91
16126 /0.401.01.41.41.41.410.919.420.623.01.21
25196 /0.401.21.41.41.51.613.623.825.628.50.78
35276 /0.401.21.61.61.61.715.527.229.332.70.554
50396 /0.401.42.02.02.02.018.132.034.638.60.386
**As per Class 5 Conductors of IS 8130:2013.Conforms to IS 694 : 2010.

Note: The number and Diameter of the conductor strands are for reference only. The size of the conductor is determined by its resistance. it may vary within the limits of related Classes and tables of IS 8130:2013.
The values given above are subject to tolrances as per relevent standards.