HFFR SINGLE CORE CABLES

Lead Free PVC Insulated Single Core Unsheathed Flexible CABLES Volatge grade Up to 1100 VOLTS IS 694:2010
Application

Used in environments where high-performance, reliability and safety is essential. Recommended for use in highly populated enclosed public areas, underground train stations. airports, hospitals, shopping malls, chemical and pharmaceuticals plants, high-tech office with electronics equipments & computers, off shore installations, nuclear power plant, etc.

Technical Data
    • Specification: IS :17048 :2018
    • Voltage Grade: Up to and Including 1100V
    • Conductor: HFFR/LSOH Halogen Free Flame Retardant cables are made of bright annealed bare / Tinned Copper of highly pure Electrolytic grade with more than 100% conductivity which makes it an excellent conductor of electricity thus helps in savings energy
Insulation Conformity: IS:17048 : 2018 Type of HFI-TP 70 (Thermoplastic) Annexure A with rated Temperature of 70°C.
  • Colour: Red, Yellow, Blue, Black, Green, Grey, White or any other colour as per customer requirement.
  • Marking: Q-FLX CABLE Z HFFR SQMM 1100V IS 17048 151 NO. 6700090011.
  • Packing: Coil in 100 and 200 m in polythene wrapping.
Insulation Variants
Product TypeSpecification
Crosslinked thermoset -70°CIS :17048: 2018 TYPE OF HFI- XL -70 C ANNEXURE A ,IS: 8130 : 2013
Crosslinked thermoset -90°CIS :17048: 2018 TYPE OF HFI- XL -90 C ANNEXURE A ,IS: 8130 : 2013
TECHNICAL SPECIFICATION SINGLE CORE HFFR INSULATED UNSHEATHED CABLE 1100 V
Nominal Area of ConductorNumber and Nominal Diameter of WireNominal Thickness of insulation Maximum Overall DiameterCurrent Carrying CapacityMaximum DC conductor resistance at 20 C
mm2mmmmmm(Amps)Ohm/km
0.516/0.200.62.6539.00
0.7524/0.200.62.8926.00
132/0.200.63.01519.50
1.530/0.200.63.42013.3
2.550/0.250.74.1287.98
456/0.300.84.8364.95
684/0.300.85.3473.30
1080/0.401.07.0651.91
16126/0.401.08.1861.21
25196/0.401.210.21030.780
35276/0.401.211.71320.554
50396/0.401.413.91740.386
70357/0.51.416.02580.272
95475/0.51.618.23040.206

As per Class 5 Conductors of IS 8130:2013.Conforms to IS 17048: 2018.

Note: The number and Diameter of the conductor strands are for reference only. The size of the conductor is determined by its resistance. it may vary within the limits of related Classes and tables of IS 8130:2013.
The values given are subject to tolerances as per relevent standards.